XC1-24R-E XINJE XC1 Series PLC AC220V DI 12 DO 12 Relay new in box
- Model: XC1-24R-E
- Shipping Weight: 1Kg
- In Stock:20
- Manufactured by: Xinje




 0 reviews
                                        0 reviews                                         
                                    | XC1-24R-E XINJE XC1 Series PLC AC220V DI 12 DO 12 Relay new in box | 
Description of products
XC1-24R-E
NPN 12 input and Relay 12 or Transistor (T) output
E (AC220V) power supply
Cannot expand with expansion module
BD board and clock
Support power-off retentive
Support basic logic control and data operation
General Specifications
| Item | Specification | 
| Insulation Voltage | Above DC 500V 2MΩ | 
| Noise Resistance | 1000V 1uS pulse for 1 minute | 
| Environment Temperature | 0°C~60°C | 
| Ambient Humidity | 5%~95% | 
| COM 1 | RS-232, be connected to host machine or HMI for programming or debugging | 
| COM 2 | RS-485/RS-232,network or connect to intelligent instrument, inverter, etc. | 
| Installation | M3 screw fixed or DIN46277 (35mm width) guide rail installation | 
| Grounding | The third type grounding (Never perform common grounding with strong power system) | 
Functional Specifications
| Item | Specification | |
| Program Operation Mode | Circulation scanning mode, timing scanning mode | |
| Program Mode | Instructions and ladder chart | |
| Dispose Speed | 0.5us | |
| Power Failure Holding | FlashROM | |
| User Program’s Capacity | 32K | |
| I/O Points | 12 input points,12 output points | |
| Output Format | Relay | |
| Power Supply | E: AC220V C: DC24V | |
| Interior Coil’s Points (M) | 576 points | |
| 
 Timer(T) | Points | 80 points | 
| Specification | 100mS timer: set time 0.1~3276.7 seconds | |
| 
 Counter(C) | Points | 48 Points | 
| Specification | 16 bits counter: set value K0~32767 32 bits counter: set value 214748364~ + 2147483647 | |
| Data Register(D) | 406 characters | |
| FlashROM Register(FD) | 510 characters | |
| High-speed Count Format | - | |
| Timing Scanning Interval Setting | 0~99mS | |
| Password Protection | 6 characters ASCII | |
| Self-diagnose Function | Power on self-diagnose, monitor timer, grammar check | |