SV015IG5-1 VFD inverter 1.5KW 200V 1 phase NEW
- Model: SV015IG5-1
- Shipping Weight: 3Kg
- In Stock:10
- Manufactured by: LS
SV015IG5-1 VFD inverter 1.5KW 200V 1 phase NEW |
Specification 200~230V
Drive Type (SV_ _ _iG5-_) |
004-1 |
008-1 |
015-1 |
004-2 |
008-2 |
015-2 |
022-2 |
037-2 |
040-2 |
|
Motor Rating |
[HP] |
0.5 |
1 |
2 |
0.5 |
1 |
2 |
3 |
5 |
5.4 |
[kW] |
0.37 |
0.75 |
1.5 |
0.37 |
0.75 |
1.5 |
2.2 |
3.7 |
4 |
|
Output ratings |
Capacity[kVA] |
1.1 |
1.9 |
3 |
1.1 |
1.9 |
3 |
4.5 |
6.1 |
6.5 |
FLA[A] |
3 |
5 |
8 |
3 |
5 |
8 |
12 |
16 |
17 |
|
Frequency |
0 ~ 400 Hz |
|||||||||
Voltage |
200 ~ 230V |
|||||||||
Input ratings |
Voltage |
1 phase 200 ~ 230 V( 10%) 3 phase 200 ~ 230 V( 10%) |
||||||||
Frequency |
50 ~ 60 Hz ( 5%) 50 ~ 60 Hz ( 5%) |
|||||||||
Weight[kg] |
|
1.2 |
1.8 |
2.1 |
1.2 |
1.2 |
1.8 |
2.1 |
2.2 |
2.2 |
|
Braking circuit |
On board |
||||||||
Average braking torque |
20% (with optional external braking resistor : 100%, 150%) |
|||||||||
Braking torque |
Max.continuous braking time |
15 seconds |
||||||||
Max. duty |
0 ~ 30 % ED |
|||||||||
Cooling method |
|
Forced air cooling Natura |
||||||||
Enclosure |
|
IP00 |
Specification 380~460V
Drive Type (SV_ _ _iG5-_) |
004-4 |
008-4 |
015-4 |
022-4 |
037-4 |
040-4 |
|||
Motor Rating |
[HP] |
0.5 |
1 |
2 |
3 |
5 |
5.4 |
||
[kW] |
0.37 |
0.75 |
1.5 |
2.2 |
3.7 |
4 |
|||
Output ratings |
Capacity[kVA] |
1.1 |
1.9 |
3 |
4.5 |
6.1 |
6.5 |
||
FLA[A] |
1.1 |
2.5 |
4 |
6 |
8 |
9 |
|||
Input ratings |
Voltage |
3 phase 380 ~ 460 V( 10%) |
|||||||
Frequency |
50 ~ 60 Hz ( 5%) |
||||||||
Weight[kg] |
Weight [kg] |
1.7 |
1.7 |
1.8 |
2.1 |
2.2 |
2.2 |
||
|
Braking circuit |
On board |
|||||||
Braking torque |
Average braking torque |
20% (with optional external braking resistor : 100%, 150%) |
|||||||
Max. continuous braking time |
15 seconds |
||||||||
Max. duty |
0 ~ 30 % ED |
||||||||
Cooling method |
Forced air cooling |
||||||||
Enclosure |
IP00 |
||||||||
Control
|
Control method |
V/F control |
|||||||
Frequency setting resolution |
Digital reference : 0.01 Hz (below 100 Hz), 0.1 Hz (over 100 Hz) Analog reference : 0.03 Hz / 50 Hz |
||||||||
Frequency accuracy |
Digital : 0.01% of max. output frequency Analog : 0.1% of max. output frequency |
||||||||
V/F ratio |
Linear, Square pattern, User V/F |
||||||||
Overload capacity |
150 % of rated current for 1 min., 200% of rated current for 0.5 sec. (characteristic is inversely proportional to time) |
||||||||
Torque boost |
Manual torque boost (0 ~ 15 %), Auto torque boost |
||||||||
operation |
Input signal |
Operation method |
Keypad / terminal / communication operation |
||||||
Frequency setting |
Analog : 0 ~ 10V / 4 ~ 20 mA Digital : keypad |
||||||||
Start signal |
Forward, Reverse |
||||||||
Multi-step |
Up to 8 speeds can be set (use multi-function terminal) |
||||||||
Multi-step accel/decel time |
0 ~ 6,000 sec, up to 8 types can be set and selected for each setting (use the multi- function terminal) |
||||||||
Accel/Decel pattern : linear pattern, U pattern, S pattern, Optimum, Minimum |
|||||||||
Emergency stop |
Interrupts the output of the drive |
||||||||
Jog |
Jog operation |
||||||||
Fault reset |
Resets fault when protective function is active |
||||||||
Output signal |
Operation status |
Frequency level detection, Overload alarm, stalling, overvoltage, undervoltage, drive overheating, running, stop, |
|||||||
constant speed, speed searching |
|||||||||
Fault output |
Contact output (30A,30C,30B) - AC250V 1A, DC30V 1A |
||||||||
Indicator |
Choose 1 from output frequency, output current, output voltage, DC voltage (Output pulse: 500Hz, Output voltage: 0 ~ 10V) |
||||||||
Operation function |
DC braking, frequency limit, frequency jump, second function, slip compensation, reverse rotation prevention, |
|
auto restart, PID control |
||
Protective function |
Drive trip |
Overvoltage, undervoltage, overcurrent, drive overheating, motor over heating, input/output phase loss, |
|
input/output mis-wiring, overload protection, communication error, loss of speed command, hardware faul |
|
Inverter alarm |
Stall prevention, overload alarm |
|
Momentary power loss |
Less than 15 msec : continuous operation, more than 15 msec : auto restart possible |
|
Display Keypad |
Operation information |
Output frequency, output current, output voltage, frequency value setting, operating speed, DC voltage |
Trip information |
Indicates the fault when the protection function activates, memorizes up to 5 faults |
|
Environment |
Ambient temperature |
-10 °C ~ 40 °C |
Storage temperature |
-20 °C ~ 65 °C |
|
Ambient humidity |
90 % RH max.(Non condensing) |
|
Altitude . Vibration |
Below 1,000 m below 5.9m/sec2(=0.6g) |
|
Application site |
No corrosive gas, combustible gas, oil mist, or dust |
There are currently no product reviews.