N2-401-H3 TECO 3 phase 400V 2.3A output 0.75KW 1HP Inverter VFD frequency AC drive NEW

  • Model: N2-401-H3
  • Shipping Weight: 4Kg
  • In Stock:20
Qty:          Favorite

Payment method Shipping method Contact us


0 reviews


 

1

Product Specifications

1/ 3 Phase 200-240 Volts

N2-xxx—xxx

2P5

201

202

203

205

208

210

215

220

230

Horse Power

1/2

 

1

2

3

5

7.5

10

15

20

30

Rated Motor KW

0.4

0.75

1.5

2.2

3.7

5.5

7.5

11

15

22

Rated Current (A)

3.1

4.5

7.5

10.5

17.5

26

35

49

64

87

Output (KVA)

1.2

1.7

2.9

4.0

6.7

9.9

13.3

18.7

24.4

33.2

Input Voltage Max.

(1 / 3 Phase) (200~240 Volts +-10%) (50/60Hz +-5%) (5 h.p. & above 3 Phase Only)

Output Voltage Max.

3 Phase 200 ~ 240 (proportional to input voltage)

IP20 Weight (Kg)

1.4

1.4

2.5

4.0

4.0

6.8

7.1

12.3

12.5

13.8

Power Loss

Ride Through (s)

1

1

2

2

2

2

2

2

2

2

3 Phase 380 ~ 480 Volts

N2-xxx—xxx

401

402

403

405

408

410

415

420

430

Horse Power

1

 

2

3

5

7.5

10

15

20

30

Rated Motor KW

0.75

1.5

2.2

3.7

5.5

7.5

11

15

22

Rated Current (A)

2.3

3.8

5.2

8.8

13

17.5

25

32

48

Output (KVA)

1.7

2.9

4.0

6.7

9.9

13.3

19.1

24.4

36.6

Input Voltage Max

( 3 Phase 380 ~ 480 Volts +- 10%) (50/60Hz +- 5%)

Output Voltage Max.

3 Phase 380 ~ 480 Volts (proportional to input voltage)

IP20 Weight (Kg)

2.4

2.5

3.8

4.0

7.0

7.3

12.3

12.5

13.5

Power Loss

Ride Through (s)

1

1

2

2

2

2

2

2

2

Functional Specification

Control

Characteristics

Carrier frequency

1 - 12 K

Frequency Control Range

0.1 – 400 Hz

Frequency Accuracy

Digital: 0.01%  (-10 ~ 40 °C); Analog: 0.4%  (25+-10 °C)

Frequency Resolution

0.01 Hz with computer or PLC control, 0.1 Hz with keypad control when freq.

above 100 Hz

Frequency Setting Signal

(0-5VDC)  (0-10VDC)  (4-20mA) (0-20mA)

Accel / Decel Time

0.1-3600 SEC with  (2) S-curves

Braking Torque

About 20% (built-in Braking transistor)

V/F Pattern

18 patterns, one curve programmable

Protection Function

Instantaneous Over Current

Approx. 200% rated current

Overload

T-verter: 150% / 1 minute

Motor Overload Protection

Electronic thermal overload relay

Over voltage

200V series: (DC bus voltage exceeds 427V)

400v series: (DC bus voltage exceeds 854V)

Under voltage

200V series: (DC bus voltage drops < 200V)          

400v series: (DC bus voltage drops < 400V)

Momentary Power Loss

0~2 seconds: The T-verter can be restarted using the speed search feature 

Heat Sink Fin Overheat

Protected by thermister

Ground Fault

Electronic circuit protection

Operation Conditions

Input Signal

Operation signals

Forward/Reverse operation, by keypad or hardwire contact, multiple individual commands

Reset

Released protection while the protective function is operating

Multifunction Input

Refer to function illustration in Fn_56

Output Signal

Multifunction Output

Refer to function illustration in Fn_61

  Fault output

250VAC 1A, 30VDC 1A or less

Built-in Function

Frequency reference bias/gain; up/lower limit; manual torque boost; frequency meter calibrating gain; auto restart attempt; skip frequency; S-curve ACCEL/DECEL; Carrier frequency adjust.(1-12KHz)

Communication link function

Digital operator monitor

Frequency command, output frequency, speed, output current, output voltage, P-N bus voltage, rotating direction 

Analog Output Monitor

Analog output (0-10V), possible to select output frequency & setting freq. & output voltage & P-N bus voltage

Environmental

Location

Indoor (protected from corrosive gas and dust) 

Ambient Temperature

-10 degrees ~ 40 degrees © 50 degrees with cover removed 

Humidity

0-95%(non condensing)

Vibration

0.5G

Enclosure

IP20 / IP65 (NEMA4)

EMC

EN50081-1, EN50082-2 (with optional filter)

LVD

EN50178

UL

UL 508C

N2-205 and above capacity are not CE complied

Wiring

 

1

There are currently no product reviews.

1 2 3 4 5
Five Stars
NOTE: HTML tags are not allowed.
NOTE: Reviews require prior approval before they will be displayed