FX3G-14MT/ES-A PLC Main Unit DI 8 DO 6 Transistor 100 to 240V AC new |
Generic specifications
Item |
Specification |
|||||
Ambient temperature |
0 to 55°C (32 to 131°F) when operating and -25 to 75°C (-13 to 167°F) when stored |
|||||
Ambient humidity |
5 to 95%RH (no condensation) when operating |
|||||
Vibration resistance *1 |
|
Frequency (Hz) |
Acceleration (m/s2) |
Half amplitude (mm) |
Sweep Count for X, Y, Z: 10 times (80 min in each direction) |
|
When installed on DIN rail |
10 to 57 |
-- |
0.035 |
|||
57 to 150 |
4.9 |
-- |
||||
When installed directly |
10 to 57 |
-- |
0.075 |
|||
57 to 150 |
9.8 |
-- |
||||
Shock resistance *1 |
147m/s2 Acceleration, Action time: 11ms, 3 times by half-sine pulse in each direction X, Y, and Z |
|||||
Noise resistance |
By noise simulator at noise voltage of 1,000Vp-p,noise width of 1μs, rise time of 1ns and period of 30 to 100Hz |
|||||
Dielectric withstand voltage*2 |
1.5kV AC for one minute |
Between each terminals*2and ground termina |
||||
500V AC for one minute |
||||||
Insulation resistance *2 |
5MΩor more by 500V DC megger |
|||||
Grounding |
Class D grounding (grounding resistance: 100Ωor less) <Common grounding with a heavy electrical system is not allowed.>*3 |
|||||
Working atmosphere |
Free from corrosive or flammable gas and excessive conductive dusts |
|||||
Working altitude |
<2000m*4 |