FX2N-80MR-001 PLC Main Unit DI 40 DO 24 Relay AC 220V new
- Model: FX2N-80MR-001
- Shipping Weight: 2Kg
- In Stock:20
- Manufactured by: Mitsubishi
FX2N-80MR-001 PLC Main Unit DI 40 DO 24 Relay AC 220V new |
General Specifications [Main Unit]
Item |
Ambient temperature |
|||||
Ambient temperature |
0 to 55°C (32 to 131°F) when operating and -25 to 75°C (-13 to 167°F) when stored |
|||||
Ambient humidity |
5 to 95%RH (no condensation) when operating |
|||||
Vibration resistance |
Conforms to EN 68-2-6 |
|||||
|
Frequency (Hz) |
Acceleration (m/s 2 ) |
Half amplitude (mm) |
Sweep Count for X, Y, Z: 10 times (80 min in each direction) |
||
When installed on DIN rail |
10 to 57 |
-- |
0.035 |
|||
57 to 150 |
4.9 |
-- |
||||
When installed directly |
10 to 57 |
-- |
0.075 |
|||
57 to 150 |
9.8 |
-- |
||||
Shock resistance |
Compliant with EN 68-2-27 (147 m/s2Acceleration, Action time: 11ms, 3 times by half-sine pulse in each direction X, Y, and Z) |
|||||
Noise resistance |
By noise simulator at noise voltage of 1,000 Vp-p, noise width of 1 µs, rise time of 1 ns and period of 30 to 100 Hz |
|||||
Dielectric withstand voltage*1
|
1.5kV AC for one minute |
Compliant with JEM-1021 Between each terminals*1 and ground terminal |
||||
500V AC for one minute |
||||||
Insulation resistance*1 |
5MΩ or more by 500V DC megge |
|||||
Grounding |
Class D grounding (grounding resistance: 100Ω or less) <Common grounding with a heavy electrical system is not allowed.>*2 |
|||||
Working atmosphere |
Free from corrosive or flammable gas and excessive conductive dusts |
|||||
Working altitude |
Compliant with IEC61131-2 (<2000m)*3 |
*1
Terminal |
Dielectric strength |
Insulation resistance |
Between power supply terminal (AC power) and ground terminal |
1.5 kV AC for one minute |
5MΩ or more by 500V DC megger |
Between power supply terminal (DC power) and ground terminal |
500V AC for one minute |
|
Between input terminal (24V DC) and ground terminal |
500V AC for one minute |
|
Between output terminal (relay) and ground terminal |
1.5 kV AC for one minute |
|
Between output terminal (transistor) and ground terminal |
500V AC for one minute |
There are currently no product reviews.