DVP32ES200T Delta ES2 Series Standard PLC DI 16 DO 16 Transistor 100-240VAC new in box
- Model: DVP32ES200T
- Shipping Weight: 1Kg
- In Stock:20
- Manufactured by: Delta
DVP32ES200T Delta ES2 Series Standard PLC DI 16 DO 16 Transistor 100-240VAC new in box |
Features
ES2 series is a small PLC for basic sequential control. It is economical, highly efficient and functional.
Specifications
*MPU points: 16 / 20 / 24 / 32 / 40 / 60
*Program capacity: 16k steps
*Built-in with 3 COM ports: 1 RS-232 port and 2 RS-485 ports, all are able to operate independently (Master/Slave)
*Max. I/O points: 256 input points + 16 output points, or 256 output points + 16 input points
*DVP-EX2 MPU is built in with 12-bit 4AD/2DA and offers analog/temperature modules of 14-bit resolution.
*Built-in with 8 high-speed input points (2 points for 100kHz, 6 points for 10kHz) and supports U/D, U/D Dir, A/B counting modes
*New motion control instructions: Close loop control, alignment mark, shield, immediate variable speed, S-Curve acceleration/deceleration
*Application in emerging industry: Exclusive instructions and function blocks designed for PV solar tracker
*Handy instructions for frequency inverter: For controlling the forward running, reverse running, RUN and STOP of Delta's AC motor drives
*Password protection: Password for subroutine, user ID, restriction on trial times
*Highly efficient instruction efficient instruction execution
Model Item |
16ES2 00_ |
24ES2 00_ |
32ES2 00_ |
40ES2 00_ |
60ES2 00_ |
20EX2 00_ |
32ES2 11T |
|
Power supply voltage |
100 ~ 240VAC (-15% ~ 10%), 50/60Hz + - 5% |
24VDC (-15~+20%) |
||||||
Connector |
European standard removable terminal block (Pin pitch: 5mm) |
|||||||
Operation |
ES 200 |
DVP-ES2 starts to run when the power rises to 95 ~ 100VAC and stops when the power drops to 70VAC. If the power is suddenly cut off, the MPU will continue running for 10ms. |
||||||
ES 211 |
DVP-ES2 starts to run when the power rises to 20.4VDC~28.8VDC and stops when the power drops to 17.5VDC. If the power is suddenly cut off, the MPU will continue running for 10ms. |
|||||||
Power supply fuse |
2A/250VAC |
2.5A / 30VDC, Polyswitch |
||||||
Power consumption |
30VA |
|
||||||
DC24V current output |
500mA |
/ |
||||||
Power supply protection |
DC24V output short circuit protection |
/ |
||||||
Voltage withstand |
1,500VAC (Primary-secondary), 1,500VAC (Primary-PE), 500VAC (Secondary-PE) |
|||||||
Insulation resistance |
> 5M Ohm at 500VDC (between all I/O points and ground) |
|||||||
Noise immunity |
ESD: 8KV Air Discharge EFT: Power Line: 2KV, Digital I/O: 1KV, Analog & Communication I/O: 1KV RS: 26MHz ~ 1GHz, 10V/m |
|||||||
Grounding |
The diameter of grounding wire shall not be less than that of L, N terminal of the power supply. (When many PLCs are in use at the same time, please make sure every PLC is properly grounded.) |
|||||||
Environment |
Operation: 0°C~55°C (temperature), 50~95% (humidity), pollution degree 2 Storage: -25°C~70°C (temperature), 5~95% (humidity) |
|||||||
Agency approvals |
UL508 European community EMC Directive 89/336/EEC and Low Voltage Directive 73/23/EEC |
|||||||
Vibration/shock immunity |
International standards: IEC61131-2, IEC 68-2-6 (TEST Fc)/ IEC61131-2 & IEC 68-2-27 (TEST Ea) |
|||||||
Weight (g) |
R |
377 |
414 |
489 |
554 |
696 |
462 |
/ |
T |
351 |
387 |
432 |
498 |
614 |
442 |
321 |
There are currently no product reviews.