DVP06XA-S Delta S Series PLC Analog I/O Module AI4 AO2 new in box
- Model: DVP06XA-S
- Shipping Weight: 1Kg
- In Stock:20
- Manufactured by: Delta
DVP06XA-S Delta S Series PLC Analog I/O Module AI4 AO2 new in box |
Description
1. DVP06XA-S is able to receive 4 points of analog input signals (voltage or current) and convert them into 12-bit digital signals. DVP06XA-S receives 2 groups of
12-bit digital data from the PLC MPU and converts them into 2 points of analog signals for output (in voltage/current). There are 49 16-bit control registers (CR) in DVP06XA-S, and the data in it can be read and written by using FROM/TO instructions in DVP Slim series PLC MPU program.
2. The system version of DVP06XA-S can be updated via RS-485 communication. The power unit is separate from it and is small in size and easy to install.
3. The user can select voltage or current input by wiring. Range of voltage input: +-10VDC (resolution: 5mV). Range of current input: +-20mA (resolution: 20uA).
4. The user can also select voltage or current output by wiring. Range of voltage output: 0V ~ +10VDC (resolution: 2.5mV). Range of current output: 0mA ~ 20mA (resolution: 5uA).
Specifications
Mixed analog/digital (A/D) module |
Voltage input |
Current input |
Power supply voltage |
24VDC (20.4VDC ~ 28.8VDC) (-15% ~ +20%) |
|
Analog input channel |
4 channels per module |
|
Analog input range |
+-10V |
+-20mA |
Digital data range |
+-2,000 |
+-1,000 |
Resolution |
12 bits (1LSB=5mV) |
11 bits (1LSB=20uA) |
Input impedance |
200KΩ and above |
250Ω |
Overall accuracy |
+-0.5% of full scale of 25°C (77°F). +-1% of full scale during 0 ~ 55°C (32 ~ 131°F). |
|
Response time |
3ms × channels |
|
Isolation method |
There is no isolation between channels |
|
Absolution input range |
+-15V |
+-32mA |
Digital data format |
2’s complement of 16-bit, (13 significant bits) |
|
Average function |
Yes (CR#2 ~ CR#5 can be set and the range is K1 ~ K4,095) |
|
Self diagnostic function self detection |
Upper bound and lower bound detection per channel |
|
Mixed digital/analog (D/A) module |
Voltage output |
Current output |
Analog signal output channels |
2 channel per module |
|
Analog output range |
0 ~ 10V |
0 ~ 20mA |
Digital data range |
0 ~ 4,000 |
0 ~ 4,000 |
Resolution |
12 bits (1LSB=2.5mV) |
12 bits (1LSB=5uA) |
Output impedance |
0.5Ωor lower |
|
Overall accuracy |
+-0.5% of full scale of 25°C (77°F). +-1% of full scale during 0 ~ 55°C (32 ~ 131°F) |
|
Response time |
3ms × channels |
|
Max. output current |
20mA (1KΩ ~ 2MΩ) |
/ |
Tolerance carried impedance |
/ |
0 ~ 500Ω |
Digital data format |
2’s complement of 16-bit, (13 significant bits). |
|
Isolation method |
Isolation between digital and analog circuitry. There is no isolation between channels. |
|
Protection |
Voltage output has short circuit protection but long period of short circuit may cause internal wiring damage and current output break. |
|
Communication mode (RS-485) |
MODBUS ASCII/RTU Mode. Communication baud rate of 4,800/9,600/19,200/38,400/57,600/115,200. For ASCII mode, date format is 7 bits, even, 1 stop bit (7, E, 1). For RTU mode, date format is 8 bits, even, 1 stop bit (8, E, 1). The RS-485 is disabled when the DVP06XA-S is connected in series with MPU. |
|
Connect to DVP-PLC MPU in series |
When DVP06XA-S modules are connected to an MPU, the modules are numbered from 0-7. 0 is the closest to the MPU and 7 is the furthest. The Maximum number of modules is 8 modules and they do not occupy any digital I/O points of the MPU. |
|
Power supply |
||
Maximum power consumption |
2W at 24VDC (20.4VDC ~ 28.8VDC) (-15% ~ +20%), supplied by external power |
|
Environment |
||
Operation/storage |
Operation: 0°C ~ 55°C (temperature); 50 ~ 95% (humidity); pollution degree 2. Storage: -25°C ~70°C (temperature); 5 ~ 95% (humidity). |
|
Vibration/shock immunity |
International standards: IEC 61131-2, IEC 68-2-6 (TEST Fc)/IEC 61131-2 & IEC 68-2-27 (TEST Ea) |