DVP04TC-S Delta S Series PLC Temperature Measurement Module new in box

  • Model: DVP04TC-S
  • Shipping Weight: 1Kg
  • In Stock:20
  • Manufactured by: Delta
Qty:          Favorite

Payment method Shipping method Contact us


0 reviews


DVP04TC-S Delta S Series PLC Temperature Measurement Module new in box

Introduction

DVP04TC-S is able to receive 4 points of external thermocouple temperature sensors and convert them into 14-point digital signals. Besides, through FROM/TO instructions in DVP Slim series MPU program, the data in the module can be read and written. There are many 16-bit control registers (CR) in DVP04TC-S. The power unit is separate from it and is small in size and easy to install. 

Electrical Specifications

Power supply voltage

24VDC (20.4VDC ~ 28.8VDC) (-15% ~ +20%)

Max. rated power

consumption

2W, supplied by external power.

Operation/storage

Operation: 0°C~55°C (temperature), 5~95% (humidity), pollution degree 2

Storage: -25°C~70°C (temperature), 5~95% (humidity)

Vibration/shock

resistance

International standards: IEC61131-2, IEC 68-2-6 (TEST Fc)/

IEC61131-2 & IEC 68-2-27 (TEST Ea)

Series connection to

DVP-PLC MPU

The modules are numbered from 0 to 7 automatically by their distance from MPU. No.0 is the closest to MPU and No.7 is the furthest. Maximum 8 modules are allowed to connect to MPU and will not occupy any digital I/O points.

Functional Specifications

DVP04TC-S

Celsius (°C)

Fahrenheit (°F)

 

Analog input channel

4 channels per module

 

Sensors type

J-type, K-type, R-type, S-type, and T-type thermocouple

Temperature input

range

 

J-type: -100°C ~ 700°C

K-type: -100°C ~ 1,000°C

R & S type : -10°C ~ 1,700°C

T-type : -100°C ~ 350°C

 

J-type: -148°F ~ 1,292°F

K-type: -148°F ~ 1,832°F

R & S type : -14°F ~ 3,092°F

T-type : -148°F ~ 662°F

 

Digital conversion

range

 

J-type: K-1,000 ~ K7,000

K-type: K-1,000 ~ K10,000

R & S type : K-100 ~ K17,000

T-type : K-1,000 ~ K3,500

 

J-type: K-3,280 ~ K12,920

K-type: K-1,480 ~ K18,320

R & S type : K-140 ~ K30,920

T-type : K-1,480 ~ K6,620

Resolution

16 bits (0.1°C)

16 bits (0.1°F)

 

Overall accuracy

0.5% of full scale of 25°C (77°F),

1% of full scale during 0 ~ 55°C (32 ~ 131°F).

 

Response time

200ms × channels

Isolation method

 

Isolation between digital and analog circuits. There is isolation

between channels.

500VDC between digital circuits and Ground

500VDC between analog circuits and Ground

500VDC between analog circuits and digital circuits

500VDC between 24VDC and Ground

Digital data format

2’s complement of 16-bit

 

Average function

Yes (CR#2 ~ CR#5)

Self diagnostic function

Yes

 

Communication mode

(RS-485)

 

Yes (CR#32). RS-485 is disabled when the DVP04TC-S is

connected in series with an MPU.

 

 

There are currently no product reviews.

1 2 3 4 5
Five Stars
NOTE: HTML tags are not allowed.
NOTE: Reviews require prior approval before they will be displayed