DVP04PT-S Delta S Series PLC Temperature Measurement Module new in box
- Model: DVP04PT-S
- Shipping Weight: 1Kg
- In Stock:20
- Manufactured by: Delta
|
Introduction
DVP04PT-S is able to receive 4 points of platinum temperature sensors and convert them into 16-bit digital signals. Besides, through FROM/TO instructions in DVP Slim series MPU program, the data in DVP04PT-S can be read and written. There are many 16-bit control registers (CR) in DVP04PT-S. The power unit is separate from it and is small in size and easy to install.
Electrical Specification
Power supply voltage |
24VDC (20.4VDC ~ 28.8VDC) (-15% ~ +20%) |
Max. rated power consumption |
2W, supplied by external power |
Operation/storage |
Operation: 0°C~55°C (temp.), 5~95% (humidity), pollution degree 2 Storage: -25°C~70°C (temp.), 5~95% (humidity) |
Vibration/shock resistance |
International standards: IEC61131-2, IEC 68-2-6 (TEST Fc)/ IEC61131-2 & IEC 68-2-27 (TEST Ea) |
Series connection to DVP-PLC MPU |
The modules are numbered from 0 to 7 automatically by their distance from MPU. No.0 is the closest to MPU and No.7 is the furthest. Maximum 8 modules are allowed to connect to MPU and will not occupy any digital I/O points. |
Functional Specifications
DVP04PT-S |
Celsius (°C) |
Fahrenheit (°F) |
Analog input channel |
4 channels per module |
|
Sensors type |
2-wire/3-wire PT100/ Ni100/ PT1000/ Ni100 3850 PPM/°C (DIN 43760 JIS C1604-1989) |
|
Current excitation |
1.53mA / 204.8uA |
|
Temperature input range |
Please refer to the temperature/digital value characteristic curve. |
|
Digital conversion range |
Please refer to the temperature/digital value characteristic curve |
|
Resolution |
16 bits (0.1°C) |
16 bits (0.1°F) |
Overall accuracy |
+-0.6% of full scale during 0 ~ 55°C (32 ~ 131°F) |
|
Response time |
200ms × channels |
|
Isolation method |
Isolation between digital and analog circuitry. There is no isolation between channels. 500VDC between digital circuits and Ground 500VDC between analog circuits and Ground |
|
Isolation method |
500VDC between analog circuits and digital circuits 500VDC between 24VDC and Ground |
|
Digital data format |
2’s complement of 16-bit |
|
Average function |
Yes (CR#2 ~ CR#5) |
|
Self diagnostic function |
Yes |
|
Communication mode (RS-485) |
Yes (CR#32). RS-485 is disabled when the DVP04PT-S is connected in series with an MPU. |
There are currently no product reviews.