DVP04DA-S PLC 4AO Module new in box new in original

Introduction

1.  Thank you for choosing DELTA DVP PLC Series. The analog output module of DVP04DA-S series can read/write the data of analog output module by using instructions FROM/TO via DVP-PLC SS/SA/SX/SC/SV MPU program. The analog output module receives 12-bit digital data of 4 groups from PLC MPU and converts it into 4 points analog output signal either in voltage or in current. 

2. The software version of DVP04DA-S analog output module can be updated via RS-485 communication. Power unit and module are separate. Size is small and easy to install.

3. Users can select output from voltage or current via wiring. Voltage output range is 0V ~ +10VDC (resolution is 2.5mV). Current output range is 0mA ~ 20mA (resolution is 5uA)

Specifications

Digital/Analog (2D/A) module

Voltage output

Current output

Power supply voltage

24VDC (20.4VDC ~ 28.8VDC) (-15% ~ +20%)

Analog input channel

2 channels/each module

Analog output range

0 ~ 10V

0 ~ 20mA

Digital data range

0 ~ 4,000

0 ~ 4,000

Resolution 

12 bits (1LSB=2.5mV)

12 bits (1LSB=5uA)

Output impedance

0.5Ωor lower

Overall accuracy

+-0.5% of full scale of 25°C (77°F). 

+-1% of full scale during 0 ~ 55°C (32 ~ 131°F).

Response time

3ms × channels

Max. output current

20mA (1KΩ ~ 2MΩ)

--

Tolerance carried impedance

--

0 ~ 500Ω

Digital data format

2’s complementary of 16-bit, 13 significant bits.

Isolation method

Isolation between digital area and analog area. But no isolation among channels.

Protection

Voltage output has short circuit protection but a long period short circuit may cause internal wire damage and current output break. 

Communication mode

(RS-485)

Yes, communication formats are (4,800/9,600/19,200/38,400/57,600/115,200

bps). Communication format: ASCII mode is 7 bits, even bit, 1 stop bit (7, E, 1). Communication format of RTU mode is 8 bits, even bit, 1 stop bit (8, E, 1).When connecting to PLC MPU in series, RS-485 can’t be used.

Connect to DVP-PLC MPU in series

If DVP04DA-S modules are connected to MPU, the modules are numbered from 0 - 7. 0 is the closest and 7 is the furthest to the MPU. 8 modules is the max and they DO NOT occupy any digital I/O points of the MPU.

Max. rated power

consumption

24VDC (20.4VDC ~ 28.8VDC) (-15% ~ +20%), 4W, supply from external power.

Operation/storage

Operation: 0°C ~ 55°C (temperature); 50 ~ 95% (humidity); pollution degree 2.

Storage: -25°C ~70°C (temperature); 5 ~ 95% (humidity).

Vibration/shock immunity

International standards: IEC 61131-2, IEC 68-2-6 (TEST Fc)/IEC 61131-2 & IEC 68-2-27 (TEST Ea)

 