DVP04AD-SL Delta S Series PLC Left-Side High-Speed Analog I/O Module AI4 new in box

  • Model: DVP04AD-SL
  • Shipping Weight: 1Kg
  • In Stock:20
  • Manufactured by: Delta
Qty:          Favorite

Payment method Shipping method Contact us


0 reviews


DVP04AD-SL Delta S Series PLC Left-Side High-Speed Analog I/O Module AI4 new in box


The analog input module of DVP04AD-SL series can read/write the data of analog input module by using instructions FROM/TO via DVP SV/EH2-L MPU program. The analog input module receives 16bit digital data of 4 groups from PLC MPU and converts it into 4 points analog input signal either in voltage or in current. Users can select input from voltage or current via wiring. Voltage input range is -10V~10VDC (resolution is 312.5uV). Current input range is -20mA ~ 20mA (resolution is 625nA).Introduction

Electrical Specifications

Analog/Digital module

Voltage input

Current input

Power supply voltage

24VDC (-15% ~ +20%) / 3.5W

DVPPS01(PS02): input 100-240VAC, output 24VDC/1A(PS02: 2A)

Analog input channel

4 channels / each module

Range of analog input

+-10V

+-5V

+-20mA

0 ~ 20mA

4 ~ 20mA

Range of digital

conversion

+-32,000

+-32,000

+-32,000

0~32,000

0~32,000

Hardware Resolution

16 bits

16 bits

16 bits

15 bits

15 bits

Input impedance

< 0.5Ω

Overall accuracy

+-0.3% when in full scale (25°C, 77°F)

+-0.5% when in full scale within the range of 0 ~ 55°C (32 ~ 131°F)

Response time

250us / each channel

Max. output current

1KΩ ~ 2MΩ

--

Tolerance carried

impedance

--

0Ω~500Ω

Digital data format

2’s complement of 16 bits, 15 significant bits

Isolation method

Optical coupler isolation between digital circuits and analog circuits.

No isolation among analog channels.

500VDC between digital circuits and Ground

500VDC between analog circuits and Ground 

500VDC between analog circuits and digital circuits 

500VDC between 24VDC and Ground

Series connection to DVP-PLC MPU

Connectable to the left side of MPU, numbered from 100 to 107 according to the position of module from the closest to farthest to MPU.

Operation/storage

temperature

Operation: 0°C~55°C (temp.), 50~95% (humidity), Pollution degree2

Storage: -25°C~70°C (temp.), 5~95% (humidity)

Vibration/shock

immunity

International standards: IEC61131-2, IEC 68-2-6 (TEST Fc)/

IEC61131-2 & IEC 68-2-27 (TEST Ea)

 

 

There are currently no product reviews.

1 2 3 4 5
Five Stars
NOTE: HTML tags are not allowed.
NOTE: Reviews require prior approval before they will be displayed