DVP04AD-SL Delta S Series PLC Left-Side High-Speed Analog I/O Module AI4 new in box
- Model: DVP04AD-SL
- Shipping Weight: 1Kg
- In Stock:20
- Manufactured by: Delta
DVP04AD-SL Delta S Series PLC Left-Side High-Speed Analog I/O Module AI4 new in box |
The analog input module of DVP04AD-SL series can read/write the data of analog input module by using instructions FROM/TO via DVP SV/EH2-L MPU program. The analog input module receives 16bit digital data of 4 groups from PLC MPU and converts it into 4 points analog input signal either in voltage or in current. Users can select input from voltage or current via wiring. Voltage input range is -10V~10VDC (resolution is 312.5uV). Current input range is -20mA ~ 20mA (resolution is 625nA).Introduction
Electrical Specifications
Analog/Digital module |
Voltage input |
Current input |
|||
Power supply voltage |
24VDC (-15% ~ +20%) / 3.5W DVPPS01(PS02): input 100-240VAC, output 24VDC/1A(PS02: 2A) |
||||
Analog input channel |
4 channels / each module |
||||
Range of analog input |
+-10V |
+-5V |
+-20mA |
0 ~ 20mA |
4 ~ 20mA |
Range of digital conversion |
+-32,000 |
+-32,000 |
+-32,000 |
0~32,000 |
0~32,000 |
Hardware Resolution |
16 bits |
16 bits |
16 bits |
15 bits |
15 bits |
Input impedance |
< 0.5Ω |
||||
Overall accuracy |
+-0.3% when in full scale (25°C, 77°F) +-0.5% when in full scale within the range of 0 ~ 55°C (32 ~ 131°F) |
||||
Response time |
250us / each channel |
||||
Max. output current |
1KΩ ~ 2MΩ |
-- |
|||
Tolerance carried impedance |
-- |
0Ω~500Ω |
|||
Digital data format |
2’s complement of 16 bits, 15 significant bits |
||||
Isolation method |
Optical coupler isolation between digital circuits and analog circuits. No isolation among analog channels. 500VDC between digital circuits and Ground 500VDC between analog circuits and Ground 500VDC between analog circuits and digital circuits 500VDC between 24VDC and Ground |
||||
Series connection to DVP-PLC MPU |
Connectable to the left side of MPU, numbered from 100 to 107 according to the position of module from the closest to farthest to MPU. |
||||
Operation/storage temperature |
Operation: 0°C~55°C (temp.), 50~95% (humidity), Pollution degree2 Storage: -25°C~70°C (temp.), 5~95% (humidity) |
||||
Vibration/shock immunity |
International standards: IEC61131-2, IEC 68-2-6 (TEST Fc)/ IEC61131-2 & IEC 68-2-27 (TEST Ea) |
There are currently no product reviews.