CIMR-TB4V0004BBA VFD inverter input 3ph 380V output 3ph 0~480V 3.4A 0.75KW 0~400Hz New

  • Model: CIMR-TB4V0004BBA
  • Shipping Weight: 3Kg
  • In Stock:20
  • Manufactured by: Yaskawa
Qty:          Favorite

Payment method Shipping method Contact us


0 reviews


CIMR-TB4V0004BBA VFD inverter  input 3ph 380V output 3ph 0~480V 3.4A 0.75KW 0~400Hz New

Specification

Item

Specification

CIMR-T□4V

0001

0002

0004

0005

0007

0009

0011

0018

0023

0031

0038

Maximum Applicable Motor Capacity

(kW)

ND Rating

0.4

0.75

1.5

2.2

3.0

3.7

5.5

7.5

11.0

15.0

18.5

HD Rating

0.2

0.4

0.75

1.5

2.2

3.0

3.7

5.5

7.5

11.0

15.0

Input

Input Current (A)

ND Rating

1.2

2.1

4.3

5.9

8.1

9.4

14.0

20.0

24.0

38.0

44.0

HD Rating

1.2

1.8

3.2

4.4

6.0

8.2

10.4

15.0

20.0

29.0

39.0

Output

Output Current (kVA)

ND Rating

0.9

1.6

3.1

4.1

5.3

6.7

8.5

13.3

17.5

23.6

29.0

HD Rating

0.9

1.4

2.6

3.7

4.2

5.5

7.0

11.3

13.7

18.3

23.6

Output Current (A)

ND Rating

1.2

2.1

4.1

5.4

6.9

8.8

11.1

17.5

23.0

31.0

38.0

HD Rating

1.2

1.8

3.4

4.8

5.5

7.2

9.2

14.8

18.0

24.0

31.0

Overload Tolerance

ND Rating: 120% of rated output current for 60 s

HD Rating: 150% of rated output current for 60 s

(Derating may be required for applications that start and stop frequently)

Carrier Frequency

2 kHz (user-adjustable from 2 to 15 kHz)

Maximum Output Voltage (V)

Three-phase: 380 to 480 V (proportional to input voltage)

Maximum Output Frequency (Hz)

400 Hz (user-adjustable)

Power

Supply

Rated Voltage Rated Frequency

Three-phase: 380 to 480 V 50/60 Hz

Allowable Voltage Fluctuation

-15 to 10%

Allowable Frequency Fluctuation

±5%

Harmonic Corrective Actions

DC Reactor

Optional

Total Loss (W)

ND Rating

19.6

32.4

47.3

66.3

87.0

95.1

127.7

259.6

315.2

426.9

458.0

HD Rating

30.6

43.8

60.2

96.9

111.7

117.5

148.7

227.7

282.1

369.0

434.5

There are currently no product reviews.