AFPX-C30R  FP-X C30R  PLC control unit 24V DC DI 16 DO 14 new





































Control Units                
Model Name Power Pulse Outputs Modbus Rtu Dc Inputs Npn Outputs Pnp Outputs Relay Outputs Program Size (K)
AFPX-C30R AC100-240V No Yes 16     14 32
























































































































































































































General Specifications
Item Description
Relay output type Transistor output type
Power supply and I/O Specifications Power supply 100 to 240 V AC (AC power), 24 V DC (DC power)
Input 24V DC °C common
Output 2:00 AM 0.5 A
Service power supply 0.15 A (C14)/ 0.4 A (C30/ C60)
(AC power type only)
Performance Specifications Number of I/O points C14 Input: 8 points, Output: 6 points
C30 Input: 16 points, Output: 14 points
C60 Input: 32 points, Output: 28 points
I/O points when expanded C14 Max. 328 points (When using FP0 expansion units and add-on cassette)
C30 Max. 352 points (When using FP0 expansion units and add-on cassette)
C60 Max. 382 points (When using FP0 expansion units and add-on cassette)
Operation speed 0.32μs/step
Program memory Flash ROM built-in (no battery backup required)
Program capcity 16 ksteps (C14), 32 ksteps (C30, C60)
Basic instructions 111
Applied instructions 216
Operation memory Internal relay ® 4096 points
Timer/counter (T/C) 1024 points
Data register (DT) 12285 words (C14), 32765 (C30, C60)
Special functions Pulse catch input 14 points 14 points
Interrupt input 14 points 14 points
Analog I/O Input: Max. 24 ch, Output: Max. 12 ch (When using FP0 analog unit)
Input: Max. 4 ch (When using add-on cassette)
Volume input 2 points (C14/C30), 4 points (C60)
High-speed counter Input of main unit Single-phase: 8 ch x Max. 10 kHz Single-phase: 8 ch (High-speed: 4 ch, midium-speed: 4 ch)
2-phase: 4 ch Max. 5 kHz 2-phase: 4 ch (High-speed: 2 ch, midium-speed: 2ch)
  With high-speed single-phase:
  1 ch x Max. 100 kHz
  2 ch x Max. 80 kHz
  3 ch x Max. 60 kHz
  4 ch x Max. 50 kHz
  With high-speed 2-phase:
  1 ch x Max. 35 kHz
  2 ch x Max. 25 kHz
  With medium-speed single-phase:
  4 ch x Max. 10 kHz each
  With Medium-speed 2-phase:
  2 ch x Max. 5 kHz each
when pulse I/Ocassette installed Single-phase: 2 ch x Max. 80 kHz, 4 ch x Max. 50 kHz Pulse I/O cassette cannot be installed.
2-phase: 1 ch x Max. 30 kHz, 2 ch x Max. 25 kHz
Pulse output Input of main unit - With high-speed 2 ch x Max. 100 kHz
For linear interpolation, compositespeed: 100 kHz
With medium-speed 2 ch x Max. 20 kHz
For linear interpolation, compositespeed: 20 kHz
when pulse I/Ocassette installed 1 ch x Max. 100 kHz, 2ch x Max. 80 kHz Pulse I/O cassette cannot be installed.
Serial interface RS232C.RS485, USB, Ethernet
Network function PLC Link, Computer link, Modem, Modbus-RTU
Other functions Program editing during RUN, Constant scan, 8-digit password, Program