| General Specifications | 
| Item | 
Description | 
| Relay output type | 
Transistor output type | 
| Power supply and I/O Specifications | 
Power supply | 
100 to 240 V AC (AC power), 24 V DC (DC power) | 
| Input | 
24V DC °C common | 
| Output | 
2:00 AM | 
0.5 A | 
| Service power supply | 
0.15 A (C14)/ 0.4 A (C30/ C60) | 
| (AC power type only) | 
| Performance Specifications | 
Number of I/O points | 
C14 | 
Input: 8 points, Output: 6 points | 
| C30 | 
Input: 16 points, Output: 14 points | 
| C60 | 
Input: 32 points, Output: 28 points | 
| I/O points when expanded | 
C14 | 
Max. 328 points (When using FP0 expansion units and add-on cassette) | 
| C30 | 
Max. 352 points (When using FP0 expansion units and add-on cassette) | 
| C60 | 
Max. 382 points (When using FP0 expansion units and add-on cassette) | 
| Operation speed | 
0.32μs/step | 
| Program memory | 
Flash ROM built-in (no battery backup required) | 
| Program capcity | 
16 ksteps (C14), 32 ksteps (C30, C60) | 
| Basic instructions | 
111 | 
| Applied instructions | 
216 | 
| Operation memory | 
Internal relay ® | 
4096 points | 
| Timer/counter (T/C) | 
1024 points | 
| Data register (DT) | 
12285 words (C14), 32765 (C30, C60) | 
| Special functions | 
Pulse catch input | 
14 points | 
14 points | 
| Interrupt input | 
14 points | 
14 points | 
| Analog I/O | 
Input: Max. 24 ch, Output: Max. 12 ch (When using FP0 analog unit) | 
| Input: Max. 4 ch (When using add-on cassette) | 
| Volume input | 
2 points (C14/C30), 4 points (C60) | 
| High-speed counter | 
Input of main unit | 
Single-phase: 8 ch x Max. 10 kHz | 
Single-phase: 8 ch (High-speed: 4 ch, midium-speed: 4 ch) | 
| 2-phase: 4 ch Max. 5 kHz | 
2-phase: 4 ch (High-speed: 2 ch, midium-speed: 2ch) | 
|   | 
With high-speed single-phase: | 
|   | 
1 ch x Max. 100 kHz | 
|   | 
2 ch x Max. 80 kHz | 
|   | 
3 ch x Max. 60 kHz | 
|   | 
4 ch x Max. 50 kHz | 
|   | 
With high-speed 2-phase: | 
|   | 
1 ch x Max. 35 kHz | 
|   | 
2 ch x Max. 25 kHz | 
|   | 
With medium-speed single-phase: | 
|   | 
4 ch x Max. 10 kHz each | 
|   | 
With Medium-speed 2-phase: | 
|   | 
2 ch x Max. 5 kHz each | 
| when pulse I/Ocassette installed | 
Single-phase: 2 ch x Max. 80 kHz, 4 ch x Max. 50 kHz | 
Pulse I/O cassette cannot be installed. | 
| 2-phase: 1 ch x Max. 30 kHz, 2 ch x Max. 25 kHz | 
| Pulse output | 
Input of main unit | 
- | 
With high-speed 2 ch x Max. 100 kHz | 
| For linear interpolation, compositespeed: 100 kHz | 
| With medium-speed 2 ch x Max. 20 kHz | 
| For linear interpolation, compositespeed: 20 kHz | 
| when pulse I/Ocassette installed | 
1 ch x Max. 100 kHz, 2ch x Max. 80 kHz | 
Pulse I/O cassette cannot be installed. | 
| Serial interface | 
RS232C.RS485, USB, Ethernet | 
| Network function | 
PLC Link, Computer link, Modem, Modbus-RTU | 
| Other functions | 
Program editing during RUN, Constant scan, 8-digit password, Program |